What busway size do I need for 4000 A?

At 4000 A, the aluminium LVA straight length measures 125 × 572 mm; aluminium GMA measures 78.6 × 540 mm; and four-conductor copper GMC measures 100 × 380 mm.

These are outside dimensions, not conductor areas in mm² or installation clearances; confirm the system and configuration before reserving the route.

Selection reference

What busway size do I need for 4000 A?
System / materialCurrentWidth × height (mm)Bars
LVA · Al250 A125 × 1031 deck
LVA · Al400 A125 × 1131 deck
LVA · Al630 A125 × 1281 deck
LVA · Al800 A125 × 1431 deck
LVA · Al1000 A125 × 1681 deck
LVA · Al1250 A125 × 2031 deck
LVA · Al1350 A125 × 2031 deck
LVA · Al1600 A125 × 2531 deck
LVA · Al2000 S A125 × 2931 deck
LVA · Al2000 D A125 × 3222 decks
LVA · Al2500 A125 × 3922 decks
LVA · Al3200 A125 × 4922 decks
LVA · Al4000 A125 × 5722 decks
LVA · Al5000 A125 × 6852 decks
GMA · Al250 A78.6 × 601 per phase
GMA · Al400 A78.6 × 801 per phase
GMA · Al630 A78.6 × 1001 per phase
GMA · Al800 A78.6 × 1251 per phase
GMA · Al1000 A78.6 × 1601 per phase
GMA · Al1250 A78.6 × 2101 per phase
GMA · Al1600 A78.6 × 2501 per phase
GMA · Al2000 A78.6 × 2701 per phase
GMA · Al2500 A78.6 × 4202 per phase
GMA · Al3200 A78.6 × 5002 per phase
GMA · Al4000 A78.6 × 5402 per phase
GMC · Cu400 A100 × 604 wires
GMC · Cu630 A100 × 704 wires
GMC · Cu800 A100 × 804 wires
GMC · Cu1000 A100 × 904 wires
GMC · Cu1250 A100 × 1104 wires
GMC · Cu1600 A100 × 1404 wires
GMC · Cu2000 A100 × 1904 wires
GMC · Cu2500 A100 × 2304 wires
GMC · Cu3200 A100 × 3104 wires
GMC · Cu4000 A100 × 3804 wires
GMC · Cu5000 A100 × 4604 wires

Sources: LVA PHYS table; GM GMA DIMS and GMC CU_DIM tables.

Dimensions describe the straight-length body, excluding joints, boxes and installation clearances.

GMC uses the four-conductor column and 100 mm width.

GMA's two conductors per phase must not be confused with LVA's two decks.

More suitable if…

you define the system, current and material before comparing available space and installation with a cable solution.

Not ideal if…

you want to select conductor area in mm² from amperage alone: these tables do not state conductor area or replace electrical selection.

Frequently asked questions

What is the cross-section of a 4000 A busway?

If you mean the outside dimensions, LVA is 125 × 572 mm, GMA is 78.6 × 540 mm and four-conductor GMC is 100 × 380 mm. These tables do not state metal conductor area in mm².

What changes between aluminium and copper?

Compare each series, not just its metal: LVA and GMA use aluminium; GMC uses copper. Their outside dimensions differ at 4000 A. GMA is the usual GM option; GMC lets you specify copper.

What does single or double deck mean?

LVA 2000 S has one deck and measures 125 × 293 mm; 2000 D has two decks and measures 125 × 322 mm. LVA from 2500 to 5000 A has two decks. GMA lists one or two conductors per phase, not double decks.

Are sizes above 4000 A documented?

These sources include 5000 A LVA at 125 × 685 mm and four-conductor 5000 A GMC at 100 × 460 mm. The GMA table used stops at 4000 A; do not extrapolate its dimensions.

Is width by height the space I should reserve?

No. Allow for the joints, supports, boxes and access required for that system. Consult its manual and send your route for a layout review.

From drawing to estimate

Compare the complete route and connections, not only the straight-length size, to avoid site changes that increase installed cost against cables.

All technical guides

Specialist product · GM-Z

Are you looking for medium-voltage busway?

GM-Z is a cast-resin busway built for medium-voltage power: typically the link between generators, transformers and switchgear in power plants and large industrial sites.

It is engineered and quoted project by project. Most commercial and industrial buildings need a low-voltage system such as LVA or GM instead.

Read the GM-Z overview