Selection reference
| System / material | Current | Width × height (mm) | Bars |
|---|---|---|---|
| LVA · Al | 250 A | 125 × 103 | 1 deck |
| LVA · Al | 400 A | 125 × 113 | 1 deck |
| LVA · Al | 630 A | 125 × 128 | 1 deck |
| LVA · Al | 800 A | 125 × 143 | 1 deck |
| LVA · Al | 1000 A | 125 × 168 | 1 deck |
| LVA · Al | 1250 A | 125 × 203 | 1 deck |
| LVA · Al | 1350 A | 125 × 203 | 1 deck |
| LVA · Al | 1600 A | 125 × 253 | 1 deck |
| LVA · Al | 2000 S A | 125 × 293 | 1 deck |
| LVA · Al | 2000 D A | 125 × 322 | 2 decks |
| LVA · Al | 2500 A | 125 × 392 | 2 decks |
| LVA · Al | 3200 A | 125 × 492 | 2 decks |
| LVA · Al | 4000 A | 125 × 572 | 2 decks |
| LVA · Al | 5000 A | 125 × 685 | 2 decks |
| GMA · Al | 250 A | 78.6 × 60 | 1 per phase |
| GMA · Al | 400 A | 78.6 × 80 | 1 per phase |
| GMA · Al | 630 A | 78.6 × 100 | 1 per phase |
| GMA · Al | 800 A | 78.6 × 125 | 1 per phase |
| GMA · Al | 1000 A | 78.6 × 160 | 1 per phase |
| GMA · Al | 1250 A | 78.6 × 210 | 1 per phase |
| GMA · Al | 1600 A | 78.6 × 250 | 1 per phase |
| GMA · Al | 2000 A | 78.6 × 270 | 1 per phase |
| GMA · Al | 2500 A | 78.6 × 420 | 2 per phase |
| GMA · Al | 3200 A | 78.6 × 500 | 2 per phase |
| GMA · Al | 4000 A | 78.6 × 540 | 2 per phase |
| GMC · Cu | 400 A | 100 × 60 | 4 wires |
| GMC · Cu | 630 A | 100 × 70 | 4 wires |
| GMC · Cu | 800 A | 100 × 80 | 4 wires |
| GMC · Cu | 1000 A | 100 × 90 | 4 wires |
| GMC · Cu | 1250 A | 100 × 110 | 4 wires |
| GMC · Cu | 1600 A | 100 × 140 | 4 wires |
| GMC · Cu | 2000 A | 100 × 190 | 4 wires |
| GMC · Cu | 2500 A | 100 × 230 | 4 wires |
| GMC · Cu | 3200 A | 100 × 310 | 4 wires |
| GMC · Cu | 4000 A | 100 × 380 | 4 wires |
| GMC · Cu | 5000 A | 100 × 460 | 4 wires |
Sources: LVA PHYS table; GM GMA DIMS and GMC CU_DIM tables.
Dimensions describe the straight-length body, excluding joints, boxes and installation clearances.
GMC uses the four-conductor column and 100 mm width.
GMA's two conductors per phase must not be confused with LVA's two decks.
More suitable if…
you define the system, current and material before comparing available space and installation with a cable solution.
Not ideal if…
you want to select conductor area in mm² from amperage alone: these tables do not state conductor area or replace electrical selection.
Frequently asked questions
What is the cross-section of a 4000 A busway?
If you mean the outside dimensions, LVA is 125 × 572 mm, GMA is 78.6 × 540 mm and four-conductor GMC is 100 × 380 mm. These tables do not state metal conductor area in mm².
What changes between aluminium and copper?
Compare each series, not just its metal: LVA and GMA use aluminium; GMC uses copper. Their outside dimensions differ at 4000 A. GMA is the usual GM option; GMC lets you specify copper.
What does single or double deck mean?
LVA 2000 S has one deck and measures 125 × 293 mm; 2000 D has two decks and measures 125 × 322 mm. LVA from 2500 to 5000 A has two decks. GMA lists one or two conductors per phase, not double decks.
Are sizes above 4000 A documented?
These sources include 5000 A LVA at 125 × 685 mm and four-conductor 5000 A GMC at 100 × 460 mm. The GMA table used stops at 4000 A; do not extrapolate its dimensions.
Is width by height the space I should reserve?
No. Allow for the joints, supports, boxes and access required for that system. Consult its manual and send your route for a layout review.
From drawing to estimate
Compare the complete route and connections, not only the straight-length size, to avoid site changes that increase installed cost against cables.